- All
high intensity heaters have multiple outputs per model series.
Additional burner orifices are included with each heater that
enables the installer to increase or decrease the output of the
heater.
- A
complete range of Btu/hr outputs, 30,000 to 140,000 can be accomplished
with only four (4) different models.
- All
spark ignition control heaters shipped with 40VA transformer.
- All
millivolt control heaters shipped with thermostat.
- Non-corrosive
materials are used throughout heater construction.
|
| |

 |
| Buildings
with high ceilings, hard to heat areas, or buildings which require
only spot heating are more effectively heated using high intensity
infrared heaters. Infrared heaters operate more effectively because
they direct heat to any particular area or object without affecting
the temperature of the intervening air space. Warehouses, large high
bay manufacturing plants, factories, loading dock areas, service garages,
body shops, golf driving ranges and welding/fab shops are a few of
the more common applications for high intensity infrared heaters. |
| |

 |
|
Specifications
& Technical Data |
|
Clearance
To Combustibles |
Overall
Dimensions (") |
. |
| Series |
Model
No. |
Btu/hr |
Top |
Sides |
Back |
Below |
L |
W |
H |
Weight
(lbs.) |
Typical
Mounting Heights |
| 4000 |
4030
4040 |
30,000
40,000 |
30"
34" |
30"
30" |
30"
30" |
54"
68" |
30.25
|
19.25 |
12 |
25 |
10'-12' |
| Note:
All 4000 series heaters are shipped with a 40,000 Btu/hr
burner orifice. An additional orifice is included to convert
heater to 30,000 Btu/hr. |
| 8000 |
8050
8060
8070 |
50,000
60,000
70,000* |
36"
40"
40" |
30"
30"
30" |
30"
30"
30" |
78"
84"
84" |
45.25 |
19.25 |
12 |
34 |
13'-15' |
Note:
All 8000 series heaters are shipped with a 60,000 Btu/hr
burner orifice. Additional orifices are included to convert
to 50,000 Btu/hr and 70,000* Btu/hr.
*Available only in natural gas. |
| 9000S |
9080
9090
9100S |
80,000
90,000
100,000 |
46"
46"
48" |
40"
46"
46" |
40"
46"
46" |
104"
114"
118" |
60.5 |
21.5 |
11 |
49 |
15'-18' |
| Note:
All 9000S series heaters are shipped with 100,000 Btu/hr
orifices. Additional orifices are included to convert heater
to 80,000 or 90,000 Btu/hr. |
| 9100 |
9100
9120
9140 |
100,000
120,000
140,000* |
44"
46"
46" |
40"
46"
46" |
40"
46"
46" |
104"
114"
114" |
82.5 |
21.5 |
11 |
61 |
18'
& higher |
Note:
All 9100 series heaters are shipped with 120,000 Btu/hr
orifices. Additional orifices are included to convert to 100,000
Btu/hr and 140,000* Btu/hr.
*Available only in natural gas. |
| Warranty:
One year on controls. Ten year pro-rated on burner assembly. |
| |
|
Control
Systems Available
|
| Suffix |
Description |
Gas |
| DSP-5 |
Automatic
Spark Ignition on pilot with safety burner shutoff, 24VAC control
with intermittent pilot. (Pilot is off when heater is off) Transformer
120V/24V shipped loose with heater. |
Natural |
| LA-5 |
Automatic
Spark Ignition on pilot with safety burner shuttoff, 24VAC control
with intermittent pilot. (Pilot is off when heater is off) Transformer
120V/24V shipped loose with heater. |
Propane |
| PP |
Power
pile (self-generating) millivolt control. No outside electrical
source is required to turn heater on and off. Manually lit pilot.
Safety shutoff on pilot and burner. Power pile thermostat shipped
loose with heater. |
Natural/Propane |
| Optional
controls available, contact factory for details. |
|
| |
|
 |